Data record tests.battery-cell-voltage-and-specific-gravity.equipment.battery-nicd.maintenance

Verified 2026-10-29 Confidence: High

Battery Cell Voltage and Specific Gravity is specified for vented nickel-cadmium batteries in maintenance testing at clause 7.18.1.2.B.3 of ANSI/NETA MTS-2023. The clause calls for each monoblock or cell voltage and the total battery voltage to be measured with the charger energized in float; the clause names no specific gravity reading for a nickel-cadmium cell.

Value: vented nickel-cadmium batteries

ProvenanceANSI/NETA MTS-2023 supports data record tests.battery-cell-voltage-and-specific-gravity.equipment.battery-nicd.maintenance, which is cited on the entry Battery Cell Voltage and Specific Gravity.SOURCEANSI/NETA MTS-2023ANSI/NETA MTS-2023Licensed standard, clause 7.18.1.2.B.3DATA RECORDtests.battery-cell-voltage-and-specific-gravity.equipment.battery-nicd.maintenancetests.battery-cell-volta..Verified 2026-10-29ENTRYBattery Cell Voltage and Specific GravityBattery Cell Voltage and..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA MTS-2023Licensed standard, clause 7.18.1.2.B.3
Data recordtests.battery-cell-voltage-and-specific-gravity.equipment.battery-nicd.maintenanceVerified 2026-10-29
EntryBattery Cell Voltage and Specific GravityNo revisions
Subject
Battery Cell Voltage and Specific Gravity (Test methods)
Kind
Equipment fact
Source
ANSI/NETA MTS-2023, clause 7.18.1.2.B.3, Maintenance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA MTS-2023Publisher information page
Also stated in
  • Stated independently by FIST 3-6, section 5.3.1, page 66 (April 2020).
    Read the reference passage

    5.0 Vented NiCd Batteries - 5.3.1 Full Charge

    "The density of electrolyte in NiCd cells does not change appreciably with charge, so specific gravity does not indicate state of charge. This state can be estimated when the battery is on float. To hold battery voltage at 1.40VPC, a fully charged battery requires about 1 milliampere (excluding load current) per ampere-hour of capacity."

    FIST 3-6, section 5.3.1, page 66, April 2020. Agency copy of FIST 3-6

    The current standard governs; this passage is a public-domain description of the practice dated April 2020.

  • Stated independently by FIST 3-6, section 5.5.7, page 72 (April 2020).
    Read the reference passage

    5.0 Vented NiCd Batteries - 5.5.7 Specific Gravity

    "Specific gravity readings are only needed to determine if the electrolyte needs to be replaced."

    FIST 3-6, section 5.5.7, page 72, April 2020. Agency copy of FIST 3-6

    The current standard governs; this passage is a public-domain description of the practice dated April 2020.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-29created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.

"Data record tests.battery-cell-voltage-and-specific-gravity.equipment.battery-nicd.maintenance." Battery Testing Reference. 2026-10-29. https://www.batterytestingreference.com/data/tests.battery-cell-voltage-and-specific-gravity.equipment.battery-nicd.maintenance/.