Data record tests.battery-cell-voltage-and-specific-gravity.equipment.battery-vrla.maintenance

Verified 2026-10-29 Confidence: High

Battery Cell Voltage and Specific Gravity is specified for valve-regulated lead-acid batteries in maintenance testing at clause 7.18.1.3.B.3 of ANSI/NETA MTS-2023. The clause calls for each monoblock or cell voltage and the total battery voltage to be measured with the charger energized in float; the clause names no specific gravity reading for a valve-regulated cell.

Value: valve-regulated lead-acid batteries

ProvenanceANSI/NETA MTS-2023 supports data record tests.battery-cell-voltage-and-specific-gravity.equipment.battery-vrla.maintenance, which is cited on the entry Battery Cell Voltage and Specific Gravity.SOURCEANSI/NETA MTS-2023ANSI/NETA MTS-2023Licensed standard, clause 7.18.1.3.B.3DATA RECORDtests.battery-cell-voltage-and-specific-gravity.equipment.battery-vrla.maintenancetests.battery-cell-volta..Verified 2026-10-29ENTRYBattery Cell Voltage and Specific GravityBattery Cell Voltage and..No revisions
Provenance. Where this record comes from and where it is used: the cited source, the record itself and the entry that cites it.
Provenance: the chain from source to entry.
StepItemDetail
SourceANSI/NETA MTS-2023Licensed standard, clause 7.18.1.3.B.3
Data recordtests.battery-cell-voltage-and-specific-gravity.equipment.battery-vrla.maintenanceVerified 2026-10-29
EntryBattery Cell Voltage and Specific GravityNo revisions
Subject
Battery Cell Voltage and Specific Gravity (Test methods)
Kind
Equipment fact
Source
ANSI/NETA MTS-2023, clause 7.18.1.3.B.3, Maintenance Testing Specifications for Electrical Power Equipment and Systems, NETA. Publisher page for ANSI/NETA MTS-2023Publisher information page
Also stated in
  • Stated independently by FIST 3-6, section 4.3, page 56 (April 2020).
    Read the reference passage

    4.0 Valve-Regulated Lead-Acid (VRLA) Batteries (Gel Cells) - 4.3 Background

    "The hydrogen and oxygen are not expelled but recombined. Cells are sealed and require no water addition or specific gravity readings."

    FIST 3-6, section 4.3, page 56, April 2020. Agency copy of FIST 3-6

    The current standard governs; this passage is a public-domain description of the practice dated April 2020.

  • FIST 3-6, section 4.5.2, page 58 (April 2020).
    Read the reference passage

    4.0 Valve-Regulated Lead-Acid (VRLA) Batteries (Gel Cells) - 4.5.2 Voltage Readings

    "Place the probes across the posts of the cell so that the voltage drops across the intercell connections are not included."

    FIST 3-6, section 4.5.2, page 58, April 2020. Agency copy of FIST 3-6

    The current standard governs; this passage is a public-domain description of the practice dated April 2020.

History

Every recorded change to this data record, oldest first.
DateChange
2026-10-29created

Cite this page

Cite the governing standard for the fact itself; cite this page as the finding aid.